Description
TR2114W. Wall mount sensor with exposed 18oC – 28oC setpoint
The TR2114W combined room sensor and set point and operates with most Regulator Australia temperature controllers. The thermistor is installed in a special, vented enclosure that fits standard electrical mounting hardware and utilises a terminal block located on the rear and to ensure the thermistor is not influenced by any extraneous thermal activity in the wall space, the rear of each sensor is positively sealed. However considerable care should be taken when determining the location of the sensors so as to obtain a representative temperature for the room. The sensor should preferably be located on an internal wall; approximately 1500mm above the floor and care should be taken to avoid concealed water pipes, air ducts, and heat sources such as lights, computers etc, locations exposed to direct sunlight, or areas directly affected by the supply air stream. Corner locations should also be avoided because of the reduced air circulation. To average the temperature in a large zone multiple sensors can be connected to the controller to average the readings.
TR2113W. Wall mount sensor with exposed 20oC – 25oC setpoint
The TR2113W is similar to the TR2114W except for the operating range of 20oC-25oC.
TR2104W. Wall mount sensor with concealed 18oC-28oC setpoint
The TR2104 is similar to the TR2114W except that the 18oC -28oC setpoint is concealed.
TR4114W. Wall mount averaging sensor with exposed 18oC-28oC setpoint
The TR4114 have an exposed setpoint with knob located in the centre of the front panel which provides an easy to adjustment for the user. The TR4114 has a 4000 ohm temperature sensor for use in averaging applications.